In September 2023, Zhejiang Jinling Cooling Tower once again ushered in the Annual Reverification Test. The CTI Annual Reverification Test is carried out in the thermal performance test field of the cooling tower which established by the CTI standard at Jinling Headquarters in Zhejiang Province.The thermal performance test of the cooling tower needs to measure the dry and wet bulb temperature of the air entering the tower, the water amount entering the tower, the water temperature entering and leaving the tower, the input power of the motor, the supplementary water amount and the supplementary water temperature.The design flow rate is calculated according to the measured data in the selection table, and correct the water intake of the tower. The ratio of the revised flow rate to the design flow rate is the percentage of cooling capacity. The ratio greater than 95 is assessed as qualified.
After rigorous thermal performance testing, the test results of Zhejiang Jinling JNT series cross-flow open cooling tower, JNC series closed cooling tower, JFT series counter flow open cooling tower are 100% in line with the requirements, and have successfully passed the Annual Reverification Test in 2023.